Availability: | |
---|---|
CMC-HX_Smart Type
3phase AC 690V±15% (Standard wiring), AC380V±15% (Internal delta connection)
Ordinary squirrel cage AC asynchronous motor
15 ~ 700kW
Universal model, widely suitable for various mechanical loads. Typically used for fans, pumps, compressors, etc.
Multiple start and stop modes
Voltage exponential curve start, voltage linear curve start, current exponential curve start, and current linear curve start. Programmable kick start torque and start current limit can be applied in each mode. According to the different loads, you can choose the corresponding start curve to achieve the appropriate starting effect. The device is provided with a variety of stop modes including programmable soft stop, free stop, braking, and pump stop. Unique basic algorithm makes the motor start and stop accurately and smoothly.
Perfect protective function
It detects current and load parameters, having overcurrent, overload, underload, overheating, phase failure, short circuit, three-phase current imbalance, phase sequence detection, frequency error and other functions.
Unique load application parameters
It is built-in ten kinds of load types for users to choose. It provides a unique start control curve for each type of load to make soft start match the load, so as to achieve the best start and stop.
Fireproof material
The product of below 90KW is in plastic structure made with inflaming retarding ABS material; for the product of 90KW and above, the upper cover is in plastic structure and main frame is made of aluminium-zinc plate with features of heatproof and corrosion resistance.
Friendly man-machine interface
The use of LCD liquid crystal display panel, Chinese and English display interface makes programming and parameter adjustment more convenient
Advanced communication function
Standard Modbus RTU communication. Optional Ethernet/GPRS communication module makes user’s network connection control easier and improves the system's automation level and reliability.
Unique SCR triggering close-loop control algorithm
The unique SCR close-loop control is specially designed for standard load and heavy load. User can choose current-limit start or voltage ramp start according to load conditions so as to realize absolutely smooth start without torque oscillation.
Dual parameter function
With two sets of basic parameters, it can control two motors with different power respectively.
Analog signal control
Users can input 4-20mA or 0-20mA standard signal, and conduct upper and lower limit setting of analog to achieve the start and stop control of motor and alarm.
The data (pressure, temperature, flow, etc.) can also be transmitted via a soft starter. It is provided with 4-20mA or 0-20mA standard analog signal output function.
Powerful anti-interference property
All external control signals are subject to optoelectronic isolation, and different anti-noise levels are set to adapt to the application in special industrial environments.
Self-adaption of power frequency
Self-adaption of power frequency 50/60 makes user easy to use.
Dynamic fault memory
Up to 10 failures can be recorded, making it easy to find the cause of the malfunction.
Movable panel
The panel can be moved to equipment operating surface through machine interface for remote control.
Control power | AC110V to AC220V+15%, 50/60Hz |
Three-phase power | Standard wiring AC690V ±15% Internal delta wiring AC380V±15% |
Nominal current | 18A~780A, 20 rated values in total |
Applicable motor | Ordinary squirrel cage AC asynchronous motor |
Start mode | Voltage exponential curve; Voltage linear curve; Current exponential curve; Current linear curve. |
Stop mode | Free stop, Soft stop, Pump stop, Brake |
Logical input | Impedance 1.8 KΩ, power supply +24V |
Start frequency | Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times |
Protective function | Overcurrent, overload, underload, overheat, phase failure, three-phase current imbalance, phase sequence detection, overheat of motor and frequency error, etc. |
Protection Level | IP00, IP20 |
Cooling type | Natural cooling or forced air cooling |
Installation type | Wall mounted-vertical installation |
Installation Environment | When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -25 ~ +45°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G |
Connectors | Wiring instructions |
1L1, 3L2, 5L3 | Connect three-phase AC power, bypass contactor |
2T1, 4T2, 6T3 | Connecting a 3-phase asynchronous motor |
B1, B2, B3 | Connecting the bypass contactor |
Adapted motor power (KW) | Model of soft starter | Rated current (A) | Structure No. | Dimensions(mm) |
15 | CMC-015/6-HX | 18 | F005 | 172*320*172 |
22 | CMC-022/6-HX | 24 | ||
30 | CMC-030/6-HX | 30 | ||
37 | CMC-037/6-HX | 39 | ||
45 | CMC-045/6-HX | 45 | ||
55 | CMC-055/6-HX | 60 | ||
75 | CMC-075/6-HX | 76 | ||
90 | CMC-090/6-HX | 90 | ||
110 | CMC-110/6-HX | 110 | ||
132 | CMC-132/6-HX | 150 | F006 | 285*474*235 |
160 | CMC-160/6-HX | 180 | ||
200 | CMC-200/6-HX | 218 | ||
250 | CMC-250/6-HX | 260 | ||
300 | CMC-300/6-HX | 320 | ||
350 | CMC-350/6-HX | 370 | ||
400 | CMC-400/6-HX | 440 | F007 | 320*512*235 |
456 | CMC-456/6-HX | 500 | ||
500 | CMC-500/6-HX | 560 | ||
560 | CMC-560/6-HX | 630 | F008 | 400*647*235 |
700 | CMC-700/6-HX | 780 |
To place an order, please provide product model, specification, load and application condition to your supplier;
Special note: If client needs keyboard box to be externally placed, it is necessary to order the mounting accessoriess from manufacturer. When keyboard box is externally placed, it needs to lock the mounting fittings of external keyboard box onto door panel with its hole size of 115.5(H) * 104.2(W). For specific installation steps, please refer to our reference guide.
As the standard configuration of soft starter contains built-in current transformer, user does not need to externally connect the both.
About XICHI
XICHI is the leading manufacturer of soft starters in China. According to the voltage level of the adapted motor, our soft starters are divided into low voltage soft starters (CMC series_LX&HX&MX) and high voltage soft starters (CMV series for 3/6/9kV motors).
The product is independently developed and produced, and has passed strict testing, with a wide range of applications and high cost performance.
We sincerely invite you to become our agent or distributor. Let us work together to develop the market!
Multiple start and stop modes
Voltage exponential curve start, voltage linear curve start, current exponential curve start, and current linear curve start. Programmable kick start torque and start current limit can be applied in each mode. According to the different loads, you can choose the corresponding start curve to achieve the appropriate starting effect. The device is provided with a variety of stop modes including programmable soft stop, free stop, braking, and pump stop. Unique basic algorithm makes the motor start and stop accurately and smoothly.
Perfect protective function
It detects current and load parameters, having overcurrent, overload, underload, overheating, phase failure, short circuit, three-phase current imbalance, phase sequence detection, frequency error and other functions.
Unique load application parameters
It is built-in ten kinds of load types for users to choose. It provides a unique start control curve for each type of load to make soft start match the load, so as to achieve the best start and stop.
Fireproof material
The product of below 90KW is in plastic structure made with inflaming retarding ABS material; for the product of 90KW and above, the upper cover is in plastic structure and main frame is made of aluminium-zinc plate with features of heatproof and corrosion resistance.
Friendly man-machine interface
The use of LCD liquid crystal display panel, Chinese and English display interface makes programming and parameter adjustment more convenient
Advanced communication function
Standard Modbus RTU communication. Optional Ethernet/GPRS communication module makes user’s network connection control easier and improves the system's automation level and reliability.
Unique SCR triggering close-loop control algorithm
The unique SCR close-loop control is specially designed for standard load and heavy load. User can choose current-limit start or voltage ramp start according to load conditions so as to realize absolutely smooth start without torque oscillation.
Dual parameter function
With two sets of basic parameters, it can control two motors with different power respectively.
Analog signal control
Users can input 4-20mA or 0-20mA standard signal, and conduct upper and lower limit setting of analog to achieve the start and stop control of motor and alarm.
The data (pressure, temperature, flow, etc.) can also be transmitted via a soft starter. It is provided with 4-20mA or 0-20mA standard analog signal output function.
Powerful anti-interference property
All external control signals are subject to optoelectronic isolation, and different anti-noise levels are set to adapt to the application in special industrial environments.
Self-adaption of power frequency
Self-adaption of power frequency 50/60 makes user easy to use.
Dynamic fault memory
Up to 10 failures can be recorded, making it easy to find the cause of the malfunction.
Movable panel
The panel can be moved to equipment operating surface through machine interface for remote control.
Control power | AC110V to AC220V+15%, 50/60Hz |
Three-phase power | Standard wiring AC690V ±15% Internal delta wiring AC380V±15% |
Nominal current | 18A~780A, 20 rated values in total |
Applicable motor | Ordinary squirrel cage AC asynchronous motor |
Start mode | Voltage exponential curve; Voltage linear curve; Current exponential curve; Current linear curve. |
Stop mode | Free stop, Soft stop, Pump stop, Brake |
Logical input | Impedance 1.8 KΩ, power supply +24V |
Start frequency | Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times |
Protective function | Overcurrent, overload, underload, overheat, phase failure, three-phase current imbalance, phase sequence detection, overheat of motor and frequency error, etc. |
Protection Level | IP00, IP20 |
Cooling type | Natural cooling or forced air cooling |
Installation type | Wall mounted-vertical installation |
Installation Environment | When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -25 ~ +45°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G |
Connectors | Wiring instructions |
1L1, 3L2, 5L3 | Connect three-phase AC power, bypass contactor |
2T1, 4T2, 6T3 | Connecting a 3-phase asynchronous motor |
B1, B2, B3 | Connecting the bypass contactor |
Adapted motor power (KW) | Model of soft starter | Rated current (A) | Structure No. | Dimensions(mm) |
15 | CMC-015/6-HX | 18 | F005 | 172*320*172 |
22 | CMC-022/6-HX | 24 | ||
30 | CMC-030/6-HX | 30 | ||
37 | CMC-037/6-HX | 39 | ||
45 | CMC-045/6-HX | 45 | ||
55 | CMC-055/6-HX | 60 | ||
75 | CMC-075/6-HX | 76 | ||
90 | CMC-090/6-HX | 90 | ||
110 | CMC-110/6-HX | 110 | ||
132 | CMC-132/6-HX | 150 | F006 | 285*474*235 |
160 | CMC-160/6-HX | 180 | ||
200 | CMC-200/6-HX | 218 | ||
250 | CMC-250/6-HX | 260 | ||
300 | CMC-300/6-HX | 320 | ||
350 | CMC-350/6-HX | 370 | ||
400 | CMC-400/6-HX | 440 | F007 | 320*512*235 |
456 | CMC-456/6-HX | 500 | ||
500 | CMC-500/6-HX | 560 | ||
560 | CMC-560/6-HX | 630 | F008 | 400*647*235 |
700 | CMC-700/6-HX | 780 |
To place an order, please provide product model, specification, load and application condition to your supplier;
Special note: If client needs keyboard box to be externally placed, it is necessary to order the mounting accessoriess from manufacturer. When keyboard box is externally placed, it needs to lock the mounting fittings of external keyboard box onto door panel with its hole size of 115.5(H) * 104.2(W). For specific installation steps, please refer to our reference guide.
As the standard configuration of soft starter contains built-in current transformer, user does not need to externally connect the both.
About XICHI
XICHI is the leading manufacturer of soft starters in China. According to the voltage level of the adapted motor, our soft starters are divided into low voltage soft starters (CMC series_LX&HX&MX) and high voltage soft starters (CMV series for 3/6/9kV motors).
The product is independently developed and produced, and has passed strict testing, with a wide range of applications and high cost performance.
We sincerely invite you to become our agent or distributor. Let us work together to develop the market!
CMC-MX soft starter is suitable for starting and protecting general squirrel-cage AC asynchronous motors. Adapted motor power from 7.5kW to 280kW. It can smoothly start/stop the motor without steps, avoid mechanical and electrical shocks caused by traditional methods such as direct start, star/delta start, auto-coupling step-down start, etc.
XiChi XPQ Active Filters are used for Harmonic Reduction in Haier IOT Center. The active power harmonic filter (APF/AHF) suppresses the harmonic current on the load side to a great extent, and the overall harmonic filtering effect is obvious.
In the process of starting the motor, the soft starter gradually changes the conduction angle of the thyristor, so that the starting current of the motor rises smoothly from zero to the maximum value. The whole process runs smoothly, the reliability of the motor power supply is high, the impact torque on the mechanical load is reduced, the impact on the motor itself is small, and the service life of the motor and the entire equipment is prolonged.
The harmonic control technology of active filter equipment is one of the effective means to improve the quality of power supply. After the popularization and application of APF in the power supply system of hospital buildings, the generated harmonics can be controlled within the minimum range. Realize scientific and rational use of electricity, restrain grid pollution, improve power quality, ensure the safety of medical equipment, and bring huge economic and social benefits to users.
Project requirementsHigh voltage soft start device10KV 280kw * 8 units400kw * 6 unitsHigh voltage SVG1 unit
The use of high-voltage motor soft-start device can effectively improve the service life of the pump and the reliability of power supply. CMV series of products are widely used in electric power, building materials, chemical industry, metallurgy steel, paper making and other industries with rated voltage of 3000-10000V. It can be used well with various electromechanical equipment such as water pump, fan, compressor, pulverizer, mixer, belt conveyor, etc. It is an ideal high-voltage motor starting and protection equipment.
The VFD has achieved remarkable power-saving effect when used in the drive control of fans and pumps. It is an ideal speed control method. It not only improves the equipment efficiency, but also meets the production process requirements, and greatly reduces the equipment maintenance and repair costs, and also reduces the shutdown period.
Using VFD for speed regulation, it is convenient to realize multi-stage speed regulation of mining winches, and improve system stability and safety. It reduces operation failures and downtime, saves manpower and material resources, improves coal transportation capacity, and also has considerable indirect economic benefits.
APF is a new type of power electronic device for dynamically suppressing harmonics and compensating reactive power. It can quickly track and compensate harmonics of different sizes and frequencies. Compared with the passive filter device, the active filter device has better treatment effect, and it can mainly filter out multiple and high-order harmonics at the same time without causing resonance.
CFV9000A series high-voltage variable frequency speed regulation system, with high-speed DSP as the control core, adopts space voltage vector control technology and cell-series multi-level technology, with high reliability, easy operation and high performance as the design goals, to meet the needs of users for various load adjustments.
APF can not only compensate various harmonics, but also suppress flicker and compensate reactive power; the filtering characteristics are not affected by system impedance, etc., which can eliminate the risk of resonance with system impedance; it has an adaptive function, which can automatically track and compensate for changing Harmonics, that is, have the characteristics of high controllability and fast response.
XFC500 variable frequency drive is used in amusement ride to realize functions such as speed regulation, energy saving, and protection of mechanical equipment. With small size, light weight, large torque, high precision, strong function, high reliability, simple operation, easy communication and other functions.
The soft starter integrates motor soft start, soft stop and multi-function protection. In the heating industry, soft starters can be used in various applications of squirrel-cage asynchronous motors that do not require speed regulation, especially suitable for various pump loads or fan loads that require soft start and soft stop.
Application of CMV HV soft starter in piston pump in petrochemical industry.
Project Overview:The 1850 water pump house of Yaojie Coal and Electricity Group used oil circuit breaker to control high-voltage electricity, and reactor was used for starting, with large starting current and little protection function.
OverviewProduct model: CMV-800-10Load type: Crushing machinePhoto
Project infoLoad type: induced draft fanRated voltage: 10KVMotor rated current: 54ANumber of motor poles: 6 polesHigh voltage soft start model: CMV-900-10On-site parameter setting:Starting voltage: 65%Current limit multiple: 4 timesStartup time: 20Project infoLoad type: induced draft fanRated voltag
Frequency inverter applied to glass tempering furnace advantages: Low frequency and stable operation during standby, saving energy; The starting current is small, the impact on the power grid and machinery is small, and the service life of the equipment is prolonged; Quick start, shorten the production process and improve production efficiency; Control the frequency required for fast response, and control to meet the production process requirements.
The application of frequency inverters to plastic extruders has the advantages of reducing production energy consumption, improving productivity and product quality, and reducing the impact on the power grid during startup. The main extruder is composed of extrusion system, transmission system and heating and cooling system. The transmission part usually consists of a motor, a reduction box and a bearing.