MaxWell Medium-Voltage Variable Frequency Drive 3.3~10kV | China Suppliers & Factory for Industrial Applications

XICHI’s MAXWELL H series Variable Frequency Drives are innovative solutions designed to optimize motor performance, boost energy efficiency, and offer precise control across diverse applications. Manufactured in our state-of-the-art factory, these drives cater to the needs of various industries, With input voltage options ranging from 3.3kV to 11kV and a power range spanning from 185kW to 10000kW, XICHI provides tailored solutions for every requirement. As a leading supplier in China, we proudly support a wide array of industrial applications, including general loads like pumps, fans, compressors, and conveyor belts, as well as specialized loads such as compactors, crushers, extruders, mixers, mills, and kilns, Choose XICHI for high-quality Variable Frequency Drives that drive efficiency and performance in your operations

    Features
    01
    Input current harmonics
    Multi-pulse rectification using transformer phase shift technology, 30 pulses for 6kv systems and 48 pulses for 10kv systems. Meets IEEE519-2014 standard. Input filterless.
    02
    Input power factor
    The input transformer phase shift technology combined with cascade modules provide the reactive power required by the motor with an input power factor of up to 0.96. After the motor has passed through the high voltage inverter, no reactive power compensation equipment is required.
    03
    Output voltage waveform
    Module-cascaded technology, H-bridge inverter, module output superimposed to form multilevel, output perfect sine wave to ensure the motor work in better condition. It is adaptable to new and old motor.
    04
    Overall efficiency
    Efficiency up to 97%, better electromagnetic design for phase shifting transformers to reduce losses, and IGBT uses international first-tier brand.
    05
    Grid adaptability
    Output voltage fluctuation range -15%-+15%, frequency fluctuation -10%-+10%. Within the fluctuation range it ensures the output rated voltage by output injection harmonic control. It can work with the minimum voltage -45%. When the grid momentarily loses power, the high voltage frequency converter will enter the momentary power loss non-stop function to maintain the motor working, and if the grid is recovered before the system energy storage is depleted, the system will continue to work.
    06
    Lightning protection
    The mains input, output, control power input and communication signals are protected against lightning.
    07
    Modular design
    The control system, electrical system, power module, fan system and detecting unit adopt modular design, being highly reliable, easy to maintain and easy to operation.
    08
    All-in-one design
    10KV 1-2MW, one design for the structure size in the power section, 10KV 1-2.25MW, 10KV 200KW-1 MW and 6KV 185KW-0.8MW. Small in size and space saving.
    09
    Low voltage soft-start function
    The phase shifting transformer is switched to the grid on the high voltage side after the transformer has output a normal voltage by means of a low voltage soft start. The soft start ensures that the phase shifting transformer is switched to the grid without inrush current.
    10
    Control power
    The power supply of the control system adopts a modular design and a dual redundant power supply, with one from low voltage and one from high voltage. The core memory chip inside the control system is powered by a super capacitor to ensure the operation of data storage when the system is powered down.
    11
    Multiple motor control options
    Depending on the motor applications, VF control, vector control and direct torque control (DTC) are available to suit various motor loads.
    12
    Fault protection
    Motor overcurrent protection, output overload protection, input overvoltage and overcurrent protection, phase shifting transformer overheat protection, communication fault protection, power unit fault, output short circuit protection, IGBT overcurrent protection, operation gate open protection, etc.
    13
    Rich user interfaces
    It has interfaces for RS485, analogue input, analogue output, digital input, digital output, encoder input, power control, power output, high voltage circuit breaker control and detection, emergency stop, etc. to meet a wide range of applications.
    14
    Power module design
    Independent duct design, adaptable to various industrial applications. Interference-free fibre optic control signals. Module control adopts DSP digital control.
    15
    Master control system
    DSP+FPGA architecture is used to complete motor algorithms, logic control, fault handling, SVPWM regulation, communication, signal processing and other functions to perform motor control accurately, quickly and reliably.
    16
    Interference-free switching technology
    High-voltage frequency converter can achieve synchronous motor or asynchronous motor soft start, with motor starting from 0HZ and gradually running to the grid frequency of 50HZ. Then the motor switches from the frequency conversion state to the industrial frequency grid, with the switching process smooth and there is no impact current on the motor so as to ensure the safe operation of the motor.
    17
    Easy maintenance
    With a modular design, each part is a separate module, and it only needs to handle the corresponding module during maintenance, allowing the ventilation dust screen to be replaced or cleaned under normal operation.
    18
    Highly adaptable to the environment
    Protection class IP30; pollution class II. It meets start-up at -15℃ and can work at a maximum temperature of 55℃; Storage and transport temperature -40℃ to +70℃; The complete machine passes the Class III road transport test; Power module, control system, detection unit, electrical system and other modules pass the 0.6m drop test and vibration test.
    Basic Parameters
    Power Input
    Input voltage Voltage class 6KV or 10KV, output rated power is output when voltage fluctuation range is within -10%~+10%. Output power is derated within -45%~-10%.
    Input frequency 50Hz, frequency fluctuation range -10%~+10%
    Input current harmonic THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
    Input power factor Up to 0.96
    Power output
    Output voltage range 0~6KV or 0~10KV
    Output frequency 0-120Hz
    System efficiency Up to 97%
    Output overload Work for a long time with the load less than 105%, and inverse time protection enables within 110% ~ 160%.
    Output current harmonic THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
    Control Mode
    Control mode V/F, VC control without speed sensor, VC control with speed sensor
    Acceleration/deceleration time 0.1-3600S
    Frequency resolution Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency
    Frequency accuracy Digital setting ±0.01% max. frequency, analogue setting ±0.2% x set max. frequency
    Speed resolution Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency
    Speed accuracy ±0.5%
    Speed fluctuation ±0.3%
    Starting torque Larger than 120%
    Excitation braking Braking time 0-600S, starting frequency 0-50Hz, braking current 0-100% of rated current
    DC braking Braking time 1-600S, starting frequency 0-30Hz, braking current 0-150% of rated current
    Automatic voltage regulation When the input voltage varies within -10% to +10%, the output voltage can be kept constant automatically and the rated output voltage fluctuates by no more than ±3%.
    Machine parameters
    Cooling method Air cooling
    Protection class IP30
    Insulation class for phase shifting transformers Class H (180℃)
    Local operation mode Touch screen
    Auxiliary power supply ≥20 kVA
    Environmental adaptability
    Ambient operating temperature 0~+40℃. It can start directly at -15°C, and capacity derates for use at 40°C to 55°C.
    Ambient storage temperature -40℃~+70℃
    Ambient transport temperature -40℃~+70℃
    Relative humidity 5%-95%RH no condensation
    Altitude less than 2000m
    Installation site Indoor
    Contamination level Contamination level 3 and occasional conductive contaminants are allowed
    User interface
    Analogue input 3
    Analogue output 2
    Communication interface 2
    High voltage circuit breaker control 1
    Code plate interface 1
    Relay type dry contact output 6
    Transistorised dry contact output 4
    Multi-functional terminal input 8
    Power supply interface 380V AC
    Model Specifications
    MaxWell 6kV series
    Models Motor Power (kW) Rated output current (A) Weight (kg) Dimensions (mm)
    MaxWell-H0185-06 185 23 2030 1850*1770*2350
    MaxWell-H0200-06 200 25 2049
    MaxWell-H0220-06 220 27 2073
    MaxWell-H0250-06 250 31 2109
    MaxWell-H0280-06 280 34 2145
    MaxWell-H0315-06 315 38 2187
    MaxWell-H0355-06 355 43 2236
    MaxWell-H0400-06 400 48 2363
    MaxWell-H0450-06 450 54 2385
    MaxWell-H0500-06 500 60 2410
    MaxWell-H0560-06 560 67 2479
    MaxWell-H0630-06 630 75 2609
    MaxWell-H0710-06 710 85 2664
    MaxWell-H0800-06 800 94 2773
    MaxWell-H0900-06 900 106 2894
    MaxWell-H1000-06 1000 117 3060
    MaxWell-H1120-06 1120 131 3268
    MaxWell-H1250-06 1250 144 3502
    MaxWell-H1400-06 1400 161 3577
    MaxWell 10kV series
    Models Motor Power (kW) Rated output current (A) Weight (kg) Dimensions (mm)
    MaxWell-H0220-10 220 17 2163 1850*1770*2350
    MaxWell-H0250-10 250 19 2202
    MaxWell-H0280-10 280 21 2241
    MaxWell-H0315-10 315 24 2286
    MaxWell-H0355-10 355 26 2338
    MaxWell-H0400-10 400 29 2475
    MaxWell-H0450-10 450 33 2505
    MaxWell-H0500-10 500 36 2526
    MaxWell-H0560-10 560 40 2600
    MaxWell-H0630-10 630 45 2740
    MaxWell-H0710-10 710 51 2799
    MaxWell-H0800-10 800 56 2916
    MaxWell-H0900-10 900 63 3046
    MaxWell-H1000-10 1000 70 3225
    MaxWell-H1120-10 1120 79 3848
    MaxWell-H1250-10 1250 87 4100 2625*1895*2470
    MaxWell-H1400-10 1400 97 4180
    MaxWell-H1600-10 1600 110 4610
    MaxWell-H1800-10 1800 124 4990
    MaxWell-H2000-10 2000 138 5180
    MaxWell-H2250-10 2250 154 5573
    Frequently Asked Questions (FAQ)
    Q: What standard do the input current harmonics of the MaxWell series meet?
    The system achieves a THDI≤4% using transformer phase shift technology (30 pulses for 6kV and 48 pulses for 10kV systems), meeting the international standard IEEE 519-2014 and national standard GB/T 14549-93. No input filter is required.
    Q: Is external reactive power compensation equipment required?
    No. The input transformer phase shift technology combined with cascade modules provides the required reactive power with an input power factor of up to 0.96.
    Q: How does the system perform during grid voltage fluctuations or momentary power loss?
    The system functions continuously within an output voltage fluctuation range of -15% to +15% and can operate down to a minimum voltage of -45%. During a momentary grid power loss, the non-stop function maintains motor operation until power is recovered or system energy storage is depleted.
    Q: What motor control modes are supported?
    The MaxWell series supports V/F control, Vector Control (VC) without speed sensors, and Vector Control (VC) with speed sensors to adapt to different motor loads.
    Q: What is the environmental temperature range for operation and storage?
    The operating temperature range is 0°C to +40°C (can start directly at -15°C, with capacity derating up to 55°C). The storage and transport temperature limits are -40°C to +70°C.