MaxWell Medium-Voltage Variable Frequency Drive 3.3~10kV | China Suppliers & Factory for Industrial Applications
Features
Basic Parameters
| Power Input | |
| Input voltage |
Voltage class 6KV or 10KV, output rated power is output when voltage fluctuation range is within -10%~+10%. Output power is derated within -45%~-10%. |
| Input frequency | 50Hz, frequency fluctuation range -10%~+10% |
| Input current harmonic | THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard |
| Input power factor | Up to 0.96 |
| Power output | |
| Output voltage range | 0~6KV or 0~10KV |
| Output frequency | 0-120Hz |
| System efficiency | Up to 97% |
| Output overload | Work for a long time with the load less than 105%, and inverse time protection enables within 110% ~ 160%. |
| Output current harmonic | THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard |
| Control Mode | |
| Control mode | V/F, VC control without speed sensor, VC control with speed sensor |
| Acceleration/deceleration time | 0.1-3600S |
| Frequency resolution | Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency |
| Frequency accuracy | Digital setting ±0.01% max. frequency, analogue setting ±0.2% x set max. frequency |
| Speed resolution | Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency |
| Speed accuracy | ±0.5% |
| Speed fluctuation | ±0.3% |
| Starting torque | Larger than120% |
| Excitation braking | Braking time 0-600S, starting frequency 0-50Hz, braking current 0-100% of rated current |
| DC braking | Braking time 1-600S, starting frequency 0-30Hz, braking current 0-150% of rated current |
| Automatic voltage regulation | When the input voltage varies within -10% to +10%, the output voltage can be kept constant automatically and the rated output voltage fluctuates by no more than ±3%. |
| Machine parameters | |
| Cooling method | Air cooling |
| Protection class | IP30 |
| Insulation class for phase shifting transformers | Class H (180℃) |
| Local operation mode | Touch screen |
| Auxiliary power supply | ≥20 kVA |
| Environmental adaptability | |
| Ambient operating temperature |
0~+40℃ It can start directly at -15°C, and capacity derates for use at 40°C to 55° |
| Ambient storage temperature | -40℃~+70℃ |
| Ambient transport temperature | -40℃~+70℃ |
| Relative humidity | 5%-95%RH no condensation |
| Altitude | less than 2000m |
| Installation site | Indoor |
| Contamination level | Contamination level 3 and occasional conductive contaminants are allowed |
| User interface | |
| Analogue input | 3 |
| Analogue output | 2 |
| Communication interface | 2 |
| High voltage circuit breaker control | 1 |
| Code plate interface | 1 |
| Relay type dry contact output | 6 |
| Transistorised dry contact output | 4 |
| Multi-functional terminal input | 8 |
| Power supply interface | 380V AC |
Model Specifications
| MaxWell 6kV series | ||||
|---|---|---|---|---|
| Models | Motor Power (kW) | Rated output current (A) | Weight (kg) | Dimensions (mm) |
| MaxWell-H0185-06 | 185 | 23 | 2030 | 1850*1770*2350 |
| MaxWell-H0200-06 | 200 | 25 | 2049 | |
| MaxWell-H0220-06 | 220 | 27 | 2073 | |
| MaxWell-H0250-06 | 250 | 31 | 2109 | |
| MaxWell-H0280-06 | 280 | 34 | 2145 | |
| MaxWell-H0315-06 | 315 | 38 | 2187 | |
| MaxWell-H0355-06 | 355 | 43 | 2236 | |
| MaxWell-H0400-06 | 400 | 48 | 2363 | |
| MaxWell-H0450-06 | 450 | 54 | 2385 | |
| MaxWell-H0500-06 | 500 | 60 | 2410 | |
| MaxWell-H0560-06 | 560 | 67 | 2479 | |
| MaxWell-H0630-06 | 630 | 75 | 2609 | |
| MaxWell-H0710-06 | 710 | 85 | 2664 | |
| MaxWell-H0800-06 | 800 | 94 | 2773 | |
| MaxWell-H0900-06 | 900 | 106 | 2894 | |
| MaxWell-H1000-06 | 1000 | 117 | 3060 | |
| MaxWell-H1120-06 | 1120 | 131 | 3268 | |
| MaxWell-H1250-06 | 1250 | 144 | 3502 | |
| MaxWell-H1400-06 | 1400 | 161 | 3577 | |
| MaxWell 10kV series | ||||
|---|---|---|---|---|
| Models | Motor Power (kW) | Rated output current (A) | Weight (kg) | Dimensions (mm) |
| MaxWell-H0220-10 | 220 | 17 | 2163 | 1850*1770*2350 |
| MaxWell-H0250-10 | 250 | 19 | 2202 | |
| MaxWell-H0280-10 | 280 | 21 | 2241 | |
| MaxWell-H0315-10 | 315 | 24 | 2286 | |
| MaxWell-H0355-10 | 355 | 26 | 2338 | |
| MaxWell-H0400-10 | 400 | 29 | 2475 | |
| MaxWell-H0450-10 | 450 | 33 | 2505 | |
| MaxWell-H0500-10 | 500 | 36 | 2526 | |
| MaxWell-H0560-10 | 560 | 40 | 2600 | |
| MaxWell-H0630-10 | 630 | 45 | 2740 | |
| MaxWell-H0710-10 | 710 | 51 | 2799 | |
| MaxWell-H0800-10 | 800 | 56 | 2916 | |
| MaxWell-H0900-10 | 900 | 63 | 3046 | |
| MaxWell-H1000-10 | 1000 | 70 | 3225 | |
| MaxWell-H1120-10 | 1120 | 79 | 3848 | |
| MaxWell-H1250-10 | 1250 | 87 | 4100 | 2625*1895*2470 |
| MaxWell-H1400-10 | 1400 | 97 | 4180 | |
| MaxWell-H1600-10 | 1600 | 110 | 4610 | |
| MaxWell-H1800-10 | 1800 | 124 | 4990 | |
| MaxWell-H2000-10 | 2000 | 138 | 5180 | |
| MaxWell-H2250-10 | 2250 | 154 | 5573 | |
Frequently Asked Questions
What standards do the input current harmonics of the MaxWell series meet?
The input current harmonics achieve a THDI of 4% or less, which fully meets the international standard IEEE 519-2014 and the national standard GB/T 14549-93. It operates efficiently without needing an input filter.
Does the system require external reactive power compensation equipment?
No, it does not. The combination of input transformer phase shift technology and cascade modules provides the necessary reactive power for the motor, achieving an input power factor of up to 0.96. This eliminates the need for extra reactive power compensation devices.
How does the system handle temporary grid power losses?
The inverter features a non-stop function for momentary power loss. When the grid temporarily loses power, the system keeps the motor running using stored energy. If grid power is restored before the energy storage is depleted, the system will continue regular operation smoothly.
What motor control options are available in the MaxWell series?
To adapt to various motor loads and industrial applications, the system supports multiple control modes including V/F (Variable Frequency) control, Vector Control (VC) without speed sensors, and Vector Control (VC) with speed sensors.
Is the MaxWell series suitable for harsh environmental conditions?
Yes, the system is designed for high adaptability. It features an IP30 protection class, supports startup at temperatures as low as -15℃, and can operate in temperatures up to 55℃ (with capacity derating above 40℃). Additionally, the system components have successfully passed 0.6m drop and vibration testing.