0102030405
China CFV9000A Medium-voltage Variable Speed Drive Suppliers - 6/10kV Factory Solutions for Asynchronous Motors
Basic Parameters
| Model type | CFV9000A 2-quadrant | CFV9000A 4-quadrant | |
| Applied motor power (kW) | 200kW-12000kW | 200kW-2000kW | |
| Motor Poles Info | 4-pole motor is the standard, 6-12-pole motor is selected according to current | ||
| Rated output | Rated power (kW) | 200kW-12000kW | 200kW-2000kW |
| Rated current (A) | Rated current of motor rated voltage | ||
| Overload capacity | 105% continuous, 130% allow 1 minute, 150% allow 3 seconds, 180% immediate protection | 150% continuous, 180% allow 1 minute, 250% immediate protection | |
| Output voltage (kV) | Three-phase: 0-6kV, (0-10kV) | ||
| Waveform | Multiplexed SPWM sine wave | ||
| Input voltage | Phase, Frequency, Voltage | Three phase, 50Hz, 6kV(10kV) | |
| Allowed volatility | Voltage: -10%~+10%, Frequency: ±5%, -15%~-35% derating for continuous operation | ||
| Basic Performance | Start frequency | 0-10Hz can be set | |
| Accuracy |
Analog setting: less than 0.3% of max frequency setting value (25±10°C) Digital setting: less than 0.1% of max frequency setting value (-10 to +50°C) |
||
| Resolution |
Analog setting: 1/2000 of the maximum frequency setting value Digital setting: 0.01HZ (below 99.99HZ), 0.1HZ (above 100HZ) |
||
| Efficiency | >98%, at rated output | ||
| Power factor | >0.95 | ||
| Control | Acceleration and deceleration time | 0.01~6000.0S, the acceleration and deceleration time can be set separately | |
| Voltage/Frequency Characteristics | Set by the set V/F curve | ||
| PID | Manually set PID parameters | ||
| Auxiliary function | V/F curve, low frequency compensation, rated current, current protection limit setting | ||
| High voltage isolation | Electromagnetic coupling, multi-channel fiber optic transmission | ||
| Control power input | AC 220V 2kVA | ||
| Run | Run operation | Local control (touch screen, cabinet door switch) operation, remote external control operation, upper computer operation (optional) | |
| Given frequency | Touch screen digital given, multi-speed given, external control analog signal (DC4 ~ 20MA) given | ||
| Running status output | Relay status output, inverter fault, alarm, running/stop and other status indication | ||
| Touch screen | Input/output voltage, input/output current, set value, fault status of each unit, running status, transformer status, bus voltage of each unit, etc. | ||
| Protection | Protection function | Motor overcurrent, whole machine overvoltage, whole machine undervoltage, unit overcurrent, unit overvoltage, unit overheating, unit input phase loss, optical fiber communication failure, etc. | |
| Environment | Applicable places | Indoor, no corrosive or conductive gas, dust, direct sunlight, below 1000 meters above sea level (can be customized for high altitude areas) | |
| Ambient temperature/humidity | -10℃~+40℃/20~90%RH without condensation | ||
| Vibration | 5m/s² (below 0.6g) | ||
| Storage temperature | -20 to +65°C (suitable for short-term storage such as transportation) | ||
| Cooling method and protection grade | Forced air cooling/IP31 | ||
Model Specifications
6KV 2-quadrant series (excluding tangent cabinet/connection cabinet)
| Specifications | Rated Capacity (kVA) | Adapted motor rated power (kW) | Adapted motor rated current (A) | Overall dimensions (W*D*H) | Weight (kG) |
|---|---|---|---|---|---|
| CFV9000A-315-6K-F | 315 | 250 | 30 | 1700*1500*1900 | 1900-2410 |
| CFV9000A-350-6K-F | 350 | 280 | 34 | ||
| CFV9000A-400-6K-F | 400 | 315 | 38 | ||
| CFV9000A-450-6K-F | 450 | 355 | 43 | ||
| CFV9000A-500-6K-F | 500 | 400 | 48 | ||
| CFV9000A-560-6K-F | 560 | 450 | 54 | ||
| CFV9000A-630-6K-F | 630 | 500 | 60 | ||
| CFV9000A-700-6K-F | 700 | 560 | 67 | ||
| CFV9000A-790-6K-F | 790 | 630 | 76 | 2200*1700*2120 | 3250-4000 |
| CFV9000A-890-6K-F | 890 | 710 | 85 | ||
| CFV9000A-1000-6K-F | 1000 | 800 | 96 | ||
| CFV9000A-1125-6K-F | 1125 | 900 | 108 | ||
| CFV9000A-1250-6K-F | 1250 | 1000 | 120 | ||
| CFV9000A-1400-6K-F | 1400 | 1120 | 135 | ||
| CFV9000A-1560-6K-F | 1560 | 1250 | 150 | 3300*1700*2420 | 4950-5600 |
| CFV9000A-1750-6K-F | 1750 | 1400 | 168 | ||
| CFV9000A-2000-6K-F | 2000 | 1600 | 192 | 3600*1700*2420 | 6900-7300 |
| CFV9000A-2250-6K-F | 2250 | 1800 | 217 | ||
| CFV9000A-2500-6K-F | 2500 | 2000 | 241 | ||
| CFV9000A-2800-6K-F | 2800 | 2250 | 270 | ||
| CFV9000A-3125-6K-F | 3125 | 2500 | 301 | ||
| CFV9000A-3500-6K-F | 3500 | 2800 | 337 | ||
| CFV9000A-4100-6K-F | 4100 | 3250 | 390 | 4600*1700*2420 | 11750 |
| CFV9000A-5000-6K-F | 5000 | 4000 | 481 | 5900*1700*2420 | 11800 |
| CFV9000A-6250-6K-F | 6250 | 5000 | 601 | 6500*1700*2620 | 12950-13600 |
10KV 2-quadrant series (excluding tangent cabinet/connection cabinet)
| Specifications | Rated Capacity (kVA) | Adapted motor rated power (kW) | Adapted motor rated current (A) | Overall dimensions (W*D*H) | Weight (kG) |
|---|---|---|---|---|---|
| CFV9000A-315-6K-T | 315 | 250 | 30 | 2200*1700*2120 | 2400-4430 |
| CFV9000A-350-6K-T | 350 | 280 | 34 | ||
| CFV9000A-400-6K-T | 400 | 315 | 38 | ||
| CFV9000A-450-6K-T | 450 | 355 | 43 | ||
| CFV9000A-500-6K-T | 500 | 400 | 48 | ||
| CFV9000A-560-6K-T | 560 | 450 | 54 | ||
| CFV9000A-630-6K-T | 630 | 500 | 60 | ||
| CFV9000A-700-6K-T | 700 | 560 | 67 | ||
| CFV9000A-790-6K-T | 790 | 630 | 76 | ||
| CFV9000A-890-6K-T | 890 | 710 | 85 | ||
| CFV9000A-1000-6K-T | 1000 | 800 | 96 | ||
| CFV9000A-1125-6K-T | 1125 | 900 | 108 | ||
| CFV9000A-1250-6K-T | 1250 | 1000 | 120 | ||
| CFV9000A-1400-6K-T | 1400 | 1120 | 135 | 3300*1700*2420 | 5520-5600 |
| CFV9000A-1560-6K-T | 1560 | 1250 | 150 | ||
| CFV9000A-1750-6K-T | 1750 | 1400 | 168 | ||
| CFV9000A-2000-6K-T | 2000 | 1600 | 192 | 3600*1700*2420 | 5850-6090 |
| CFV9000A-2250-6K-T | 2250 | 1800 | 217 | ||
| CFV9000A-2500-6K-T | 2500 | 2000 | 241 | ||
| CFV9000A-3125-6K-T | 3125 | 2500 | 301 | 5550*1700*2420 | 10000 |
10KV 4-quadrant series (excluding tangent cabinet/connection cabinet)
| Specifications | Rated Capacity (kVA) | Adapted motor rated power (kW) | Adapted motor rated current (A) | Overall dimensions (W*D*H) | Weight (kG) |
|---|---|---|---|---|---|
| CFV9000A-315-10K-T | 315 | 250 | 18 | 2800*1700*2120 | 3500-6450 |
| CFV9000A-350-10K-T | 350 | 280 | 20 | ||
| CFV9000A-400-10K-T | 400 | 315 | 23 | ||
| CFV9000A-450-10K-T | 450 | 355 | 26 | ||
| CFV9000A-500-10K-T | 500 | 400 | 29 | ||
| CFV9000A-560-10K-T | 560 | 450 | 32 | ||
| CFV9000A-630-10K-T | 630 | 500 | 36 | ||
| CFV9000A-700-10K-T | 700 | 560 | 40 | ||
| CFV9000A-790-10K-T | 790 | 630 | 45 | ||
| CFV9000A-890-10K-T | 890 | 710 | 51 | ||
| CFV9000A-1000-10K-T | 1000 | 800 | 58 | ||
| CFV9000A-1125-10K-T | 1125 | 900 | 65 | ||
| CFV9000A-1250-10K-T | 1250 | 1000 | 72 | ||
| CFV9000A-1400-10K-T | 1400 | 1120 | 81 | ||
| CFV9000A-1560-10K-T | 1560 | 1250 | 90 | ||
| CFV9000A-1750-10K-T | 1750 | 1400 | 101 | ||
| CFV9000A-2000-10K-T | 2000 | 1600 | 115 | ||
| CFV9000A-2250-10K-T | 2250 | 1800 | 130 | 4100*1700*2420 | 9250-9400 |
| CFV9000A-2500-10K-T | 2500 | 2000 | 144 | ||
| CFV9000A-2800-10K-T | 2800 | 2250 | 162 | ||
| CFV9000A-3125-10K-T | 3125 | 2500 | 180 | ||
| CFV9000A-3500-10K-T | 3500 | 2800 | 202 | 4400*1700*2420 | 9900-9950 |
| CFV9000A-3940-10K-T | 3940 | 3150 | 227 |
6KV All-in-one series (Switch cabinet included)
| Specifications | Rated Capacity (kVA) | Adapted motor rated power (kW) | Adapted motor rated current (A) | Overall dimensions (W*D*H) | Weight (kG) |
|---|---|---|---|---|---|
| CFV9000A-315-6K-F | 315 | 250 | 30 | 2700*1500*1900 | 1900-2410 |
| CFV9000A-350-6K-F | 350 | 280 | 34 | ||
| CFV9000A-400-6K-F | 400 | 315 | 38 | ||
| CFV9000A-450-6K-F | 450 | 355 | 43 | ||
| CFV9000A-500-6K-F | 500 | 400 | 48 | ||
| CFV9000A-560-6K-F | 560 | 450 | 54 | ||
| CFV9000A-630-6K-F | 630 | 500 | 60 | ||
| CFV9000A-700-6K-F | 700 | 560 | 67 |
10KV All-in-one series (Switch cabinet included)
| Specifications | Rated Capacity (kVA) | Adapted motor rated power (kW) | Adapted motor rated current (A) | Overall dimensions (W*D*H) | Weight (kG) |
|---|---|---|---|---|---|
| CFV9000A-315-10K-F | 315 | 250 | 18 | 2700*1500*1900 | 2160-3100 |
| CFV9000A-350-10K-F | 350 | 280 | 20 | ||
| CFV9000A-400-10K-F | 400 | 315 | 23 | ||
| CFV9000A-450-10K-F | 450 | 355 | 26 | ||
| CFV9000A-500-10K-F | 500 | 400 | 29 | ||
| CFV9000A-560-10K-F | 560 | 450 | 32 | ||
| CFV9000A-630-10K-F | 630 | 500 | 36 | ||
| CFV9000A-700-10K-F | 700 | 560 | 40 | ||
| CFV9000A-790-10K-F | 790 | 630 | 45 | ||
| CFV9000A-890-10K-F | 890 | 710 | 51 | ||
| CFV9000A-1000-10K-F | 1000 | 800 | 58 | ||
| CFV9000A-1125-10K-F | 1125 | 900 | 65 | ||
| CFV9000A-1250-10K-F | 1250 | 1000 | 72 |
Note: The manufacturer reserves the right to modify the product. According to the user's requirements and options, the size and weight will change accordingly. After the manufacturer's product is upgraded, the performance and external dimensions of the product will change without prior notice.
Dimensions

Figure 1 - Suitable for 10KV 2000KW below; 6KV 1120KW below

Figure 2 - Suitable for 10KV 2000KW above; 6KV 1120KW above
Frequently Asked Questions
What is the applied motor power range for the CFV9000A series?
The applied motor power ranges from 200kW to 12000kW for the 2-quadrant model, and from 200kW to 2000kW for the 4-quadrant model.
What is the overload capacity of the CFV9000A drive?
The 2-quadrant model supports 105% continuous operation, 130% for 1 minute, 150% for 3 seconds, and immediate protection at 180%. The 4-quadrant model supports 150% continuous operation, 180% for 1 minute, and immediate protection at 250%.
What cooling method and enclosure protection rating does this VFD feature?
The CFV9000A uses a forced air cooling system and has an IP31 enclosure protection grade.
What are the input voltage and frequency tolerances?
The VFD allows a voltage volatility of -10% to +10% (with -15% to -35% derating for continuous operation) and frequency volatility of ±5%.
What protection functions are integrated into the CFV9000A?
It features comprehensive protection including motor overcurrent, whole machine overvoltage/undervoltage, unit overcurrent, unit overvoltage, unit overheating, unit input phase loss, and optical fiber communication failure.
Can the CFV9000A operate at high altitudes?
The standard model is designed for indoor use below 1000 meters above sea level, but it can be customized for high-altitude areas upon request.