China CFV9000A Medium Voltage Variable Speed Drive 6/10kV - Top Suppliers & Factory for High-Efficiency Solutions
Basic Parameters
| Model type | CFV9000A 2-quadrant |
CFV9000A 4-quadrant |
|
| Applied motor power (kW) | 200kW-12000kW |
200kW-2000kW |
|
4-pole motor is the standard, 6-12-pole motor is selected according to current |
|||
| Rated output | Rated power (kW) | 200kW-12000kW |
200kW-2000kW |
| Rated current (A) | Rated current of motor rated voltage |
||
| Overload capacity | 105% continuous, 130% allow 1 minute, 150% allow 3 seconds, 180% immediate protection |
150% continuous, 180% allow 1 minute, 250% immediate protection |
|
| Output voltage (kV) | Three-phase: 0-6kV, (0-10kV) |
||
| Waveform | Multiplexed SPWM sine wave |
||
| Input voltage | Phase, Frequency, Voltage |
Three phase 50Hz 6kV(10kV) |
|
| Allowed volatility |
Voltage: -10%~+10% Frequency: ±5% -15%~-35% derating for continuous operation |
||
| Basic Performance | Start frequency | 0-10Hz can be set |
|
| Accuracy |
Analog setting: less than 0.3% of max frequency setting value (25±10°C) Digital setting: less than 0.1% of max frequency setting value (-10 to +50°C) |
||
| Resolution |
Analog setting: 1/2000 of the maximum frequency setting value Digital setting: 0.01HZ (below 99.99HZ), 0.1HZ (above 100HZ) |
||
| Efficiency | >98%, at rated output |
||
| Power factor | >0.95 |
||
| Control | Acceleration and deceleration time | 0.01~6000.0S, the acceleration and deceleration time can be set separately |
|
| Voltage/Frequency Characteristics | Set by the set V/F curve |
||
| PID | Manually set PID parameters |
||
| Auxiliary function | V/F curve, low frequency compensation, rated current, current protection limit setting |
||
| High voltage isolation | Electromagnetic coupling, multi-channel fiber optic transmission |
||
| Control power input | AC 220V 2kVA |
||
| Run | Run operation | Local control (touch screen, cabinet door switch) operation, remote external control operation, upper computer operation (optional) |
|
| Given frequency | Touch screen digital given, multi-speed given, external control analog signal (DC4 ~ 20MA) given |
||
| Running status output | Relay status output, inverter fault, alarm, running/stop and other status indication |
||
| Touch screen | Input/output voltage, input/output current, set value, fault status of each unit, running status, transformer status, bus voltage of each unit, etc. |
||
| Protection function | Motor overcurrent, whole machine overvoltage, whole machine undervoltage, unit overcurrent, unit overvoltage, unit overheating, unit input phase loss, optical fiber communication failure, etc. |
||
| Environment | Applicable places | Indoor, no corrosive or conductive gas, dust, direct sunlight, below 1000 meters above sea level (can be customized for high altitude areas) |
|
| Ambient temperature/humidity | -10℃~+40℃/20~90%RH without condensation |
||
| Vibration | 5m/s2 (below 0.6g) |
||
| Storage temperature | -20 to +65°C (suitable for short-term storage such as transportation) |
||
| Cooling method and enclosure protection grade | Forced air cooling/IP31 |
||
Model Specifications
Specifications |
Rated Capacity (kVA) |
Adapted motor rated power (kW) |
Adapted motor rated current (A) |
Overall dimensions (W*D*H) |
Weight (kG) |
|---|---|---|---|---|---|
CFV9000A-315-6K-F |
315 |
250 |
30 |
1700*1500*1900 |
1900-2410 |
CFV9000A-350-6K-F |
350 |
280 |
34 |
||
CFV9000A-400-6K-F |
400 |
315 |
38 |
||
CFV9000A-450-6K-F |
450 |
355 |
43 |
||
CFV9000A-500-6K-F |
500 |
400 |
48 |
||
CFV9000A-560-6K-F |
560 |
450 |
54 |
||
CFV9000A-630-6K-F |
630 |
500 |
60 |
||
CFV9000A-700-6K-F |
700 |
560 |
67 |
||
CFV9000A-790-6K-F |
790 |
630 |
76 |
2200*1700*2120 |
3250-4000 |
CFV9000A-890-6K-F |
890 |
710 |
85 |
||
CFV9000A-1000-6K-F |
1000 |
800 |
96 |
||
CFV9000A-1125-6K-F |
1125 |
900 |
108 |
||
CFV9000A-1250-6K-F |
1250 |
1000 |
120 |
||
CFV9000A-1400-6K-F |
1400 |
1120 |
135 |
||
CFV9000A-1560-6K-F |
1560 |
1250 |
150 |
3300*1700*2420 |
4950-5600 |
CFV9000A-1750-6K-F |
1750 |
1400 |
168 |
||
CFV9000A-2000-6K-F |
2000 |
1600 |
192 |
3600*1700*2420 |
6900-7300 |
CFV9000A-2250-6K-F |
2250 |
1800 |
217 |
||
CFV9000A-2500-6K-F |
2500 |
2000 |
241 |
||
CFV9000A-2800-6K-F |
2800 |
2250 |
270 |
||
CFV9000A-3125-6K-F |
3125 |
2500 |
301 |
||
CFV9000A-3500-6K-F |
3500 |
2800 |
337 |
||
CFV9000A-4100-6K-F |
4100 |
3250 |
390 |
4600*1700*2420 |
11750 |
CFV9000A-5000-6K-F |
5000 |
4000 |
481 |
5900*1700*2420 |
11800 |
CFV9000A-6250-6K-F |
6250 |
5000 |
601 |
6500*1700*2620 |
12950-13600 |
Specifications |
Rated Capacity (kVA) |
Adapted motor rated power (kW) |
Adapted motor rated current (A) |
Overall dimensions (W*D*H) |
Weight (kG) |
|---|---|---|---|---|---|
CFV9000A-315-6K-T |
315 |
250 |
30 |
2200*1700*2120 |
2400-4430 |
CFV9000A-350-6K-T |
350 |
280 |
34 |
||
CFV9000A-400-6K-T |
400 |
315 |
38 |
||
CFV9000A-450-6K-T |
450 |
355 |
43 |
||
CFV9000A-500-6K-T |
500 |
400 |
48 |
||
CFV9000A-560-6K-T |
560 |
450 |
54 |
||
CFV9000A-630-6K-T |
630 |
500 |
60 |
||
CFV9000A-700-6K-T |
700 |
560 |
67 |
||
CFV9000A-790-6K-T |
790 |
630 |
76 |
||
CFV9000A-890-6K-T |
890 |
710 |
85 |
||
CFV9000A-1000-6K-T |
1000 |
800 |
96 |
||
CFV9000A-1125-6K-T |
1125 |
900 |
108 |
||
CFV9000A-1250-6K-T |
1250 |
1000 |
120 |
||
CFV9000A-1400-6K-T |
1400 |
1120 |
135 |
3300*1700*2420 |
5520-5600 |
CFV9000A-1560-6K-T |
1560 |
1250 |
150 |
||
CFV9000A-1750-6K-T |
1750 |
1400 |
168 |
||
CFV9000A-2000-6K-T |
2000 |
1600 |
192 |
3600*1700*2420 |
5850-6090 |
CFV9000A-2250-6K-T |
2250 |
1800 |
217 |
||
CFV9000A-2500-6K-T |
2500 |
2000 |
241 |
||
CFV9000A-3125-6K-T |
3125 |
2500 |
301 |
5550*1700*2420 |
10000 |
Specifications |
Rated Capacity (kVA) |
Adapted motor rated power (kW) |
Adapted motor rated current (A) |
Overall dimensions (W*D*H) |
Weight (kG) |
|---|---|---|---|---|---|
CFV9000A-315-10K-T |
315 |
250 |
18 |
2800*1700*2120 |
3500-6450 |
CFV9000A-350-10K-T |
350 |
280 |
20 |
||
CFV9000A-400-10K-T |
400 |
315 |
23 |
||
CFV9000A-450-10K-T |
450 |
355 |
26 |
||
CFV9000A-500-10K-T |
500 |
400 |
29 |
||
CFV9000A-560-10K-T |
560 |
450 |
32 |
||
CFV9000A-630-10K-T |
630 |
500 |
36 |
||
CFV9000A-700-10K-T |
700 |
560 |
40 |
||
CFV9000A-790-10K-T |
790 |
630 |
45 |
||
CFV9000A-890-10K-T |
890 |
710 |
51 |
||
CFV9000A-1000-10K-T |
1000 |
800 |
58 |
||
CFV9000A-1125-10K-T |
1125 |
900 |
65 |
||
CFV9000A-1250-10K-T |
1250 |
1000 |
72 |
||
CFV9000A-1400-10K-T |
1400 |
1120 |
81 |
||
CFV9000A-1560-10K-T |
1560 |
1250 |
90 |
||
CFV9000A-1750-10K-T |
1750 |
1400 |
101 |
||
CFV9000A-2000-10K-T |
2000 |
1600 |
115 |
||
CFV9000A-2250-10K-T |
2250 |
1800 |
130 |
4100*1700*2420 |
9250-9400 |
CFV9000A-2500-10K-T |
2500 |
2000 |
144 |
||
CFV9000A-2800-10K-T |
2800 |
2250 |
162 |
||
CFV9000A-3125-10K-T |
3125 |
2500 |
180 |
||
CFV9000A-3500-10K-T |
3500 |
2800 |
202 |
4400*1700*2420 |
9900-9950 |
CFV9000A-3940-10K-T |
3940 |
3150 |
227 |
Specifications |
Rated Capacity (kVA) |
Adapted motor rated power (kW) |
Adapted motor rated current (A) |
Overall dimensions (W*D*H) |
Weight (kG) |
|---|---|---|---|---|---|
CFV9000A-315-6K-F |
315 |
250 |
30 |
2700*1500*1900 |
1900-2410 |
CFV9000A-350-6K-F |
350 |
280 |
34 |
||
CFV9000A-400-6K-F |
400 |
315 |
38 |
||
CFV9000A-450-6K-F |
450 |
355 |
43 |
||
CFV9000A-500-6K-F |
500 |
400 |
48 |
||
CFV9000A-560-6K-F |
560 |
450 |
54 |
||
CFV9000A-630-6K-F |
630 |
500 |
60 |
||
CFV9000A-700-6K-F |
700 |
560 |
67 |
Specifications |
Rated Capacity (kVA) |
Adapted motor rated power (kW) |
Adapted motor rated current (A) |
Overall dimensions (W*D*H) |
Weight (kG) |
|---|---|---|---|---|---|
CFV9000A-315-10K-F |
315 |
250 |
18 |
2700*1500*1900 |
2160-3100 |
CFV9000A-350-10K-F |
350 |
280 |
20 |
||
CFV9000A-400-10K-F |
400 |
315 |
23 |
||
CFV9000A-450-10K-F |
450 |
355 |
26 |
||
CFV9000A-500-10K-F |
500 |
400 |
29 |
||
CFV9000A-560-10K-F |
560 |
450 |
32 |
||
CFV9000A-630-10K-F |
630 |
500 |
36 |
||
CFV9000A-700-10K-F |
700 |
560 |
40 |
||
CFV9000A-790-10K-F |
790 |
630 |
45 |
||
CFV9000A-890-10K-F |
890 |
710 |
51 |
||
CFV9000A-1000-10K-F |
1000 |
800 |
58 |
||
CFV9000A-1125-10K-F |
1125 |
900 |
65 |
||
CFV9000A-1250-10K-F |
1250 |
1000 |
72 |
Dimensions