Control voltage | AC110V ~ 220V ±15℅, 50/60Hz |
Mains voltage | AC 220V, AC 380V, AC 480V ± 10℅ |
Nominal current | 18A ~ 780A, 20 rated values in total |
Applicable motor | Squirrel cage AC induction motor |
Start methods | Voltage ramp start, Current ramp start, Pump start control, Direct start, Kickstart. |
Stop methods | Voltage ramp, Soft stop, Brake, Free stop, Pump stop. |
Start frequency | No more than 10 times per hour (recommended) |
IP | ≤55kW, IP00 ≥75kW, IP20 |
Cooling type | ≤55kW, Natural cooling ≥75kW, Forced air cooling |
Installation type | Wall mounted |
Communication method | RS485 (Optional) |
Environmental condition | When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -10 ~ +40°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G |
Communication expansion card
Profibus communication expansion card can be built-in.
Removeable keypad and extra large screen
Easily removable keypad for remote operation.
Motor preheating
In low-temperature environments, the motor is heated before operation without the need for external heating equipment.
More comprehensive motor protection functions
Overvoltage protection, undervoltage protection, overcurrent protection, overload protection, stall protection, bypass fault, thyristor fault, three-phase current imbalance, motor overheating protection, etc.
Pump control function
Unique start and stop control for pump loads. The pump starting function reduces the starting current of pump loads; the pump stopping function reduces the water hammer effect.
Pump cleaning function
Self-service cleaning of siltation in the pump to prevent overflow, overload and other failures caused by blocked rotor.
Fan braking function
Dynamic braking can quickly stop the running load; static braking can bring the running load to a stop state under the action of external force.
Low speed operation function
It has the functions of low-speed forward rotation and low-speed reverse rotation, and can adjust the load running direction at low speed before the motor starts normally.
Wide supply voltage range
220V-500V main power input voltage.
Motor Power /kW | Model No. | XST260 Rated Current /A | Motor Rated Current /A (standard connection) | Motor Rated Current /A (Inside Delta connection) |
---|---|---|---|---|
7.5 | XST260-0018-03 | 18 | 18 | 32 |
11 | XST260-0024-03 | 24 | 24 | 42 |
15 | XST260-0030-03 | 30 | 30 | 52 |
18.5 | XST260-0039-03 | 39 | 39 | 68 |
22 | XST260-0045-03 | 45 | 45 | 78 |
30 | XST260-0060-03 | 60 | 60 | 104 |
37 | XST260-0076-03 | 76 | 76 | 132 |
45 | XST260-0090-03 | 90 | 90 | 156 |
55 | XST260-0110-03 | 110 | 110 | 190 |
75 | XST260-0150-03 | 150 | 150 | 260 |
90 | XST260-0180-03 | 180 | 180 | 312 |
110 | XST260-0218-03 | 218 | 218 | 378 |
132 | XST260-0260-03 | 260 | 260 | 450 |
160 | XST260-0320-03 | 320 | 320 | 554 |
185 | XST260-0370-03 | 370 | 370 | 640 |
220 | XST260-0440-03 | 440 | 440 | 762 |
250 | XST260-0500-03 | 500 | 500 | 866 |
280 | XST260-0560-03 | 560 | 560 | 969 |
315 | XST260-0630-03 | 630 | 630 | 1090 |
400 | XST260-0780-03 | 780 | 780 | 1350 |