XPQ Static Var Generator, 400V/690V
Features
- 1.Compensation abilityThe system can adjust the reactive power output based on site conditions to prevent overcompensation or undercompensation, ensuring a power factor of 0.99.2.Fast responseFully digital control. The harmonic current detection utilizes an efficient TTA algorithm based on time domain exchange. This enables quick and accurate calculation of the instantaneous value of reactive current, leading to a significant improvement in compensation response time and achieving a full response within 10ms.3.High-end quality of core componentsGerman original IGBT module, three-level topology.The control system is comprised of the American TIDSP control chip, as well as ALTERA and CYCLONE 3 series FPGA chips, making it a powerful three-core system.Additionally, TI's double-ended high-speed input 12-bit A/D data conversion chip enhances the accuracy and reliability of signal sampling.4.Efficient heat dissipationThe layered heat dissipation design allows for independent air ducts, leading to improved heat dissipation performance and effectively preventing dust and other pollutants from affecting the control system.5.Independent fan, detachableThe fans can be easily disassembled and reassembled independently, enhancing heat dissipation reliability.6.Modular designVarious capacity modules can be installed in any combination to improve the reliability and maintainability of the whole machine.7.Human-Machine InterfaceSingle module can be equipped with a 5-inch LCD touchscreen, and multiple modules can have an external 7-inch LCD touchscreen.It supports real-time monitoring of operating data and online change of control parameters. It is simple to operate and can be equipped with an optional mobile phone APP for remote control.
Basic Parameters
Compensation capacity /Kvar
25
30
50
75
100
100
AC input
Rated voltage
400V(±15%)
690V (±15%)
Working frequency
(50±10%) Hz
Wiring method
3-phase 4-wire or 3-phase 3-wire
Technical Parameter
Filtering capability
≥97%;
Excess capacity is compensated at maximum capacity
Power consumption
≤3% of rated capacity
Module expansion capability
Up to 10 function modules
Switching frequency
20kHz
Circuit topology
Three-level
Compensation range
Inductive reactive power and capacitive reactive power can be continuously compensated
Filter level setting
Each harmonic can be individually set, and the ability to selectively eliminate specific harmonics (enhanced SVG) and ordinary SVG without filtering
Compensation range
Inductive reactive power, capacitive reactive power can be continuously compensated
Compensation range
The maximum inrush current
Not more than rated current
Response time
100μs/10ms
Protection function
Grid overvoltage, undervoltage, overcurrent, bus overvoltage, overheating and current limiting protection, etc., with a delay of 5μs
Display function
- Each voltage and current value, current waveform display;
- Total load current value, SVG output total current value display;
- Operation mode setting, fault and runtime inquiry.
Communication Interface
RS232, RS485; WIFI and GPRS optional
Performance
Noise
<65dB
Target power factor
-0. 99 ~ 0. 99 adjustable
Cooling method
Forced air cooling
Ambient temperature
-10℃ ~ +40℃
Storage temperature
-20℃ ~ +60℃
Humidity Maximum
Max 95%RH(non-condensing)
Altitude
Altitude ≤1500m, according to GB/T3859.2, the capacity decreases by 1% for every 100M increase
Protection grade
IP20 (other protection grades can be customized)
Mechanical characteristic
Color
Acrylic black;
other colors can be customized on request.
Operating characteristics
Operating safely and reliably 24/7 without disrupting the normal operation of other system equipment.
The module has protection measures such as overhumidity, overvoltage, undervoltage, overload and overcurrent, short circuit and system self-diagnosis function.
If a fault such as a short circuit occurs inside the module, it can protect itself without affecting the external power system.
If the compensation energy required by the load is greater than the rated compensation energy, it can be output according to the main body capacity and continue to compensate without overloading or causing equipment damage and exiting operation.
Model Specifications
Dimensions
-
Drawer type
Model No.
Dimensions (mm)
W
H
D
w
d
h
Set screw
Net weight(kg)
XPQ - SG - 4L - 030
484
200
640
465
158
610
M6
34
XPQ - SG - 4L - 050
XPQ - SG/MG - 4L - 075
XPQ - SG/MG - 4L - 100
544
250
646
525
180
610
47
XPQ - MG - 4L - 030
392
200
555
373
158
530
29
XPQ - MG - 4L - 050
392
200
555
373
158
530
29
-
Wall-mounted type
Model No.
Dimensions (mm)
W
H
D
w
d
h
Set screw
Net weight(kg)
XPQ - SG - 4L - 030
440
657
212
375
633
/
M8
35
XPQ - SG - 4L - 050
XPQ - SG/MG - 4L - 075
XPQ - SG/MG - 4L - 100
500
657
262
375
633
/
48
XPQ - MG - 4L - 030
348
577
208
275
553
/
30
XPQ - MG - 4L - 050
/
30
-
Drawer type (lightweight)
Model No.
Dimensions (mm)
W
H
D
w
d
h
Set screw
Net weight(kg)
XPQ - CG - 4L - 030
88
520
420
/
507.6
/
M6
15
XPQ - CG - 4L - 050
-
Wall-mounted (lightweight)
Model No.
Dimensions (mm)
W
H
D
w
d
h
Set screw
Net weight(kg)
XPQ - CG - 4L - 030
460
473
101.2
350
454
/
M8
15
XPQ - CG - 4L - 050