MaxWell Medium-voltage Variable Frequency Drive, 3.3~10kV
Features
- 1. Input current harmonicsMulti-pulse rectification using transformer phase shift technology, 30 pulses for 6kv systems and 48 pulses for 10kv systems.Meets IEEE519-2014 standard.Input filterless.2. Input power factorThe input transformer phase shift technology combined with cascade modules provide the reactive power required by the motor with an input power factor of up to 0.96. After the motor has passed through the high voltage inverter, no reactive power compensation equipment is required.3. Output voltage waveformModule-cascaded technology, H-bridge inverter, module output superimposed to form multilevel, output perfect sine wave to ensure the motor work in better condition. It is adaptable to new and old motor.4. Overall efficiencyEfficiency up to 97%, better electromagnetic design for phase shifting transformers to reduce losses, and IGBT uses international first-tier brand.5. Grid adaptabilityOutput voltage fluctuation range -15%-+15%, frequency fluctuation -10%-+10%. Within the fluctuation range it ensures the output rated voltage by output injection harmonic control. It can work with the minimum voltage -45%. When the grid momentarily loses power, the high voltage frequency converter will enter the momentary power loss non-stop function to maintain the motor working, and if the grid is recovered before the system energy storage is depleted, the system will continue to work.6. Lightning protectionThe mains input, output, control power input and communication signals are protected against lightning.7. Modular designThe control system, electrical system, power module, fan system and detecting unit adopt modular design, being highly reliable, easy to maintain and easy to operation.8. All-in-one design10KV 1-2MW, one design for the structure size in the power section, 10KV 1-2.25MW, 10KV 200KW-1 MW and 6KV 185KW-0.8MW. Small in size and space saving.9. Low voltage soft-start functionThe phase shifting transformer is switched to the grid on the high voltage side after the transformer has output a normal voltage by means of a low voltage soft start. The soft start ensures that the phase shifting transformer is switched to the grid without inrush current.10. Control powerThe power supply of the control system adopts a modular design and a dual redundant power supply, with one from low voltage and one from high voltage. The core memory chip inside the control system is powered by a super capacitor to ensure the operation of data storage when the system is powered down.11. Multiple motor control optionsDepending on the motor applications, VF control, vector control and direct torque control (DTC) are available to suit various motor loads.12. Fault protectionMotor overcurrent protection, output overload protection, input overvoltage and overcurrent protection, phase shifting transformer overheat protection, communication fault protection, power unit fault, output short circuit protection, IGBT overcurrent protection, operation gate open protection, etc.13. Rich user interfacesIt has interfaces for RS485, analogue input, analogue output, digital input, digital output, encoder input, power control,power output, high voltage circuit breaker control and detection, emergency stop, etc. to meet a wide range of applications.14. Power module designIndependent duct design, adaptable to various industrial applications. Interference-free fibre optic control signals. Module control adopts DSP digital control.15. Master control systemDSP+FPGA architecture is used to complete motor algorithms, logic control, fault handling, SVPWM regulation, communication, signal processing and other functions to perform motor control accurately, quickly and reliably.16. Interference-free switching technologyHigh-voltage frequency converter can achieve synchronous motor or asynchronous motor soft start, with motor starting from 0HZ and gradually running to the grid frequency of 50HZ. Then the motor switches from the frequency conversion state to the industrial frequency grid, with the switching process smooth and there is no impact current on the motor so as to ensure the safe operation of the motor.17. Easy maintenanceWith a modular design, each part is a separate module, and it only needs to handle the corresponding module during maintenance, allowing the ventilation dust screen to be replaced or cleaned under normal operation.18. Highly adaptable to the environmentProtection class IP30; pollution class II. It meets start-up at -15℃ and can work at a maximum temperature of 55℃;Storage and transport temperature -40℃to +70℃;The complete machine passes the Class III road transport test;Power module, control system, detection unit, electrical system and other modules pass the 0.6m drop test and vibration test.
Basic Parameters
Power Input
Input voltage
Voltage class 6KV or 10KV, output rated power is output when voltage fluctuation range is within -10%~+10%.
Output power is derated within -45%~-10%.
Input frequency
50Hz,frequency fluctuation range -10%~+10%
Input current harmonic
THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
Input power factor
Up to 0.96
Power output
Output voltage range
0~6KV or 0~10KV
Output frequency
0-120Hz
System efficiency
Up to 97%
Output overload
Work for a long time with the load less than 105%, and inverse time protection enables within 110% ~ 160%.
Output current harmonic
THDI≤4%, meeting international standard IEEE 519-2014 and national standard GB/T 14549-93 power quality standard
Control Mode
Control mode
V/F, VC control without speed sensor, VC control with speed sensor
Acceleration/deceleration time
0.1-3600S
Frequency resolution
Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency
Frequency accuracy
Digital setting ±0.01% max. frequency, analogue setting ±0.2% x set max. frequency
Speed resolution
Digital setting 0.01Hz, analogue setting 0.1 x set maximum frequency
Speed accuracy
±0.5%
Speed fluctuation
±0.3%
Starting torque
Larger than120%
Excitation braking
Braking time 0-600S, starting frequency 0-50Hz, braking current 0-100% of rated current
DC braking
Braking time 1-600S, starting frequency 0-30Hz, braking current 0-150% of rated current
Automatic voltage regulation
When the input voltage varies within -10% to +10%, the output voltage can be kept constant automatically and the rated output voltage fluctuates by no more than ±3%.
Machine parameters
Cooling method
Air cooling
Protection class
IP30
Insulation class for phase shifting transformers
Class H (180℃)
Local operation mode
Touch screen
Auxiliary power supply
≥20 kVA
Environmental adaptability
Ambient operating temperature
0~+40℃
It can start directly at -15°C, and capacity derates for use at 40°C to 55°
Ambient storage temperature
-40℃~+70℃
Ambient transport temperature
-40℃~+70℃
Relative humidity
5%-95%RH no condensation
Altitude
less than 2000m
Installation site
Indoor
Contamination level
Contamination level 3 and occasional conductive contaminants are allowed
User interface
Analogue input
3
Analogue output
2
Communication interface
2
High voltage circuit breaker control
1
Code plate interface
1
Relay type dry contact output
6
Transistorised dry contact output
4
Multi-functional terminal input
8
Power supply interface
380V AC
Model Specifications
-
MaxWell 6kV series
Models
Motor Power
(kW)
Rated output current
(A)
Weight
(kg)
Dimensions
(mm)
MaxWell-H0185-06
185
23
2030
1850*1770*2350
MaxWell-H0200-06
200
25
2049
MaxWell-H0220-06
220
27
2073
MaxWell-H0250-06
250
31
2109
MaxWell-H0280-06
280
34
2145
MaxWell-H0315-06
315
38
2187
MaxWell-H0355-06
355
43
2236
MaxWell-H0400-06
400
48
2363
MaxWell-H0450-06
450
54
2385
MaxWell-H0500-06
500
60
2410
MaxWell-H0560-06
560
67
2479
MaxWell-H0630-06
630
75
2609
MaxWell-H0710-06
710
85
2664
MaxWell-H0800-06
800
94
2773
MaxWell-H0900-06
900
106
2894
MaxWell-H1000-06
1000
117
3060
MaxWell-H1120-06
1120
131
3268
MaxWell-H1250-06
1250
144
3502
MaxWell-H1400-06
1400
161
3577
MaxWell 10kV series
Models
Motor Power
(kW)
Rated output current
(A)
Weight
(kg)
Dimensions
(mm)
MaxWell-H0220-10
220
17
2163
1850*1770*2350
MaxWell-H0250-10
250
19
2202
MaxWell-H0280-10
280
21
2241
MaxWell-H0315-10
315
24
2286
MaxWell-H0355-10
355
26
2338
MaxWell-H0400-10
400
29
2475
MaxWell-H0450-10
450
33
2505
MaxWell-H0500-10
500
36
2526
MaxWell-H0560-10
560
40
2600
MaxWell-H0630-10
630
45
2740
MaxWell-H0710-10
710
51
2799
MaxWell-H0800-10
800
56
2916
MaxWell-H0900-10
900
63
3046
MaxWell-H1000-10
1000
70
3225
MaxWell-H1120-10
1120
79
3848
MaxWell-H1250-10
1250
87
4100
2625*1895*2470
MaxWell-H1400-10
1400
97
4180
MaxWell-H1600-10
1600
110
4610
MaxWell-H1800-10
1800
124
4990
MaxWell-H2000-10
2000
138
5180
MaxWell-H2250-10
2250
154
5573