CMC-MX Soft Starter with internal Bypass Contactor, 380V
Features
- ● Various starting methodsUsers can select current limit start, voltage ramp start, and can apply programmable kick start and start current limit in each mode. Meet the needs of the site and achieve a good starting effect.● High reliabilityThe high-performance microprocessor digitizes the signals in the control system, avoiding the excessive adjustment of the analog circuits in the past, thereby obtaining accuracy and execution speed.● Strong anti-interferenceAll external control signals are optically isolated, and different anti-noise levels are set to adapt to use in special industrial environments.● Simple adjustment methodThe control system has a wide range of applications, the mode adjustment is simple and intuitive, and various functional options can be used to match various control objects.● Optimized structureThe unique compact internal structure design is particularly convenient for users to integrate into the existing system, saving the cost of current transformers and bypass contactors for users.● Power frequency can be setThe power frequency 50/60Hz is set by parameters, which is convenient for users to use.● Analog output4-20mA current output function, user-friendly.● MODBUS-RTU communicationDuring network communication, 32 devices can be connected. Users can achieve the purpose of automatic communication by setting the baud rate and communication address. The communication address setting range is 1-32, and the factory default value is 1. The communication baud rate setting range is: 0, 2400; 1, 4800; 2, 9600; 3, 19200; the factory value is 2 (9600).● Perfect protection functionA variety of motor protection functions (such as overcurrent, input/output phase loss, thyristor short circuit, overheat protection, leakage detection, electronic thermal overload, internal contactor fault, phase current imbalance, etc.) Not damaged during operation.● Easy maintenanceThe monitoring signal coding system composed of 4-digit digital display monitors the working conditions of the system equipment 24 hours a day, and provides fast fault diagnosis at the same time.
Basic Parameters
Applicable motor type Ordinary squirrel cage AC asynchronous motor Rated control supply voltage AC110V to AC220V+15% Supply frequency 50/60Hz Rated operation voltage Standard wiring AC380V Internal delta wiring AC380V±30% Nominal current 18A~560A, 18 rated values in total Applicable motor Ordinary squirrel cage AC asynchronous motor Start mode Current-limited soft-start, Voltage ramp start. Stop mode Free stop, Soft stop Logical input Impedance 1.8 KΩ, power supply +15V Start frequency Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times Protective function Phase failure, overcurrent, short circuit, SCR protection, overheating, underload, phase current imbalance, wiring, internal fault, etc. IP degree of protection IP00 Cooling system Natural cooling or forced air cooling Installation type Wall mounted-vertical installation Installation Environment When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -25°C to +45°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G
Model Specifications
-
Model No.
Rated Current
(A)
Applicable motor power
(kW)
Size
&
Net weight
CMC-008/3-MX
18
7.5
173*275*192mm,
5.6kg
CMC-011/3-MX
24
11
CMC-015/3-MX
30
15
CMC-018/3-MX
39
18.5
CMC-022/3-MX
45
22
CMC-030/3-MX
60
30
CMC-037/3-MX
76
37
CMC-045/3-MX
90
45
CMC-055/3-MX
110
55
CMC-075/3-MX
150
75
285*450*305mm,
25.1kg
CMC-090/3-MX
180
90
CMC-110/3-MX
218
110
CMC-132/3-MX
260
132
CMC-160/3-MX
320
160
CMC-185/3-MX
370
185
320*523*330mm,
34.5kg
CMC-220/3-MX
440
220
CMC-250/3-MX
500
250
CMC-280/3-MX
560
280
Dimensions
-
Power range
Size (mm)
G
H
I
K
L
M
E
D
A/B/C
8 ~ 55 kW
173
275
192
133
250
7
90
86
50
75 ~ 160 kW
285
450
305
230
390
9
170
158
50
185 ~ 280 kW
320
523
330
270
415
9
195
158
50
- 55kW and below
- 75kW ~ 160kW
- 185kW ~ 280kW
-
Basic Settings of Different Applications
-
(following settings are for reference only)
Load type
Initial voltage
(%)
Start ramp time
(s)
Stop ramp time
(s)
Current limit ILIM
Foreship propeller
25
10
0
2.5
Centrifugal fan
25
20
0
3.5
Centrifugal pump
25
6
6
3
Piston compressor
25
15
0
3
Hoisting machinery
30
15
6
3.5
Mixer
40
15
0
3.5
Crusher
30
15
6
3.5
Screw compressor
20
15
0
3.5
Spiral conveyor belt
25
10
6
3.5
No-load motor
25
10
0
2.5
Conveyor belt
25
15
10
3.5
Heat pump
25
15
6
3
Escalator
25
10
0
3
Air pump
25
10
0
2.5