CMC-LX 3 phase Soft Starter, AC380V, 7.5 ~ 630kW
Features
- ● Unique SCR triggering close-loop control algorithmThe unique SCR close-loop control is specially designed for standard load and heavy load. User can choose current-limit start or voltage ramp start according to load conditions so as to realize absolutely smooth start without torque oscillation.● High control precisionAdoption of high-performance Cortex-M3 32-bit inner core CPU for central control with features of fast speed, high precision and strong capability of anti-interference.● Simple and compact appearanceThree-in and six-out structure of main circuit under patent protection and built-in current transformer with easy wiring and high reliability.● Standard MODBUS-RTU protocolWhen ordering, users can choose whether to carry the standard MODBUS-RTU communication protocol according to the actual situation.● Integrated with advanced protective functionProtective functions of phase failure, overload, overcurrent, phase current unbalance, thyristor overheat to protect motor and other equipment.● Fireproof materialThe product of below 90kW is in plastic structure made with inflaming retarding ABS material; for the product of 90kW and above, the upper cover is in plastic structure and main frame is made of aluminium-zinc plate with features of heatproof and corrosion resistance.● Movable panelThe panel can be moved to equipment operating surface through machine interface for remote control.● Easy maintenanceThe monitor signal coding system consists of 4-digit display monitors working state of the equipment for 24 hours and provides fast fault diagnosis.
Basic Parameters
Control power External AC110V-10% to AC220V+15%, 50/60Hz Built-in Internal integrated control power supply, no need for external Three-phase power AC380V±15% (Standard or Internal delta wiring) Nominal current 18A~1200A, 23 rated values in total Applicable motor Squirrel cage AC asynchronous motor Start ramp mode Voltage ramp start, current ramp start Stop mode Free stop, Soft stop Logical input Impedance 1.8 KΩ, power supply +24V Start frequency Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times Protective function Phase loss, overcurrent, SCR protection, overheating, phase current imbalance IP IP00 Cooling type Natural cooling or forced air cooling Installation type Wall mounted Communication method RS485(Optional) Environmental condition When sea altitude is above 2,000m, soft starter should be derated for use.
Ambient temperature: -25 ~ +45°C
Relative humidity: less than 95% (20°C±5°C)
Free of flammable, explosive and corrosive gas or conductive dust.
Indoor installation, good ventilation, vibration less than 0.5G
Model Specifications
-
Model No.
Rated Current
(A)
Applicable motor power
(kW)
Size
&
Net weight
CMC-008/3-LX
18
7.5
320*172*172mm,
4.3kg
CMC-011/3-LX
24
11
CMC-015/3-LX
30
15
CMC-018/3-LX
39
18.5
CMC-022/3-LX
45
22
CMC-030/3-LX
60
30
CMC-037/3-LX
76
37
CMC-045/3-LX
90
45
CMC-055/3-LX
110
55
CMC-075/3-LX
150
75
CMC-090/3-LX
180
90
474*285*235mm,
18.5kg
CMC-110/3-LX
218
110
CMC-132/3-LX
260
132
CMC-160/3-LX
320
160
CMC-185/3-LX
370
185
CMC-220/3-LX
440
220
512*320*235mm,
23kg
CMC-250/3-LX
500
250
CMC-280/3-LX
560
280
CMC-315/3-LX
630
315
CMC-400/3-LX
780
400
652*400*235,
40.8kg
CMC-470/3-LX
920
470
CMC-530/3-LX
1000
530
CMC-630/3-LX
1200
630
Dimensions
-
Model
Structure
No.
G
H
I
K
L
M
A
B
C
D
Gross weight
(kg)
CMC-008~075/3-LX
F005
172
320
172
156
240
6
54
35
72
55
4.7
CMC-090~185/3-LX
F006
285
474
235
230
390
9
85
61
101
39
19.9
CMC-220~315/3-LX
F007
320
512
235
270
415
9
97.5
60
101
39
25.8
CMC-400~530/3-LX
F008
400
652
235
330
500
9
120
57
101
39
51.5
- F005
- F006 & F007 & F008
-
Applications
-
● Pumps and Fans;● Conveyors and Belt Systems;● Compressors;● Centrifuges;● Crushers and Mills;● Mixers and Agitators;● HVAC Systems;● Conveyor Belt Systems;● Mining Equipment;● Water and Wastewater Treatment.Overall, low voltage soft starters are widely used in industrial processes where controlled acceleration and deceleration of electric motors are essential for efficient and reliable operation.